UT572 is for measuring earth resistance and soil resistivity. It can automatically check interface connection and detect interference voltage/frequency, with data hold and indication functions. It can perform 2/3/4-wire measurements for different on-site applications, such as power equipment wiring and lightning protection equipment.
Specifications Range UT572
Earth resistance (Re) 4Ω ±(3%+15)
40Ω ±(3%+5)
400Ω ±(3%+5)
4kΩ ±(3%+5)
40kΩ ±(3%+5)
Soil resistivity (ρ) 4Ω ρ=2×π×L×Re (Depending on the test result of Re)
40Ω
400Ω
4kΩ
40kΩ
Disturbance voltage (Ust) 50V (DC voltage/40Hz~500Hz) ±(3%+3)
Disturbance frequency (Fst) 40Hz~500Hz ±(1%+2)
Features
2/3/4-wire test √
Earth resistance test frequency 94/128Hz √
Soil resistivity test distances 1~40m √
Earth resistance RH and RS test √
Compensating resistance RK test √
Data hold √
Data storage 20
LCD backlight √
Auto power off Around 5 minutes √