1 / 1
HIOKI
The FT3151 Analog Earth Tester uses the AC phase differential system to measure earthing resistance, which assures that accurate measurements are unaffected by earth voltage and auxiliary earthing resistance. New innovate cord winders make clean up a breeze.
Measurement system AC potentiometer method, Three-electrode method/ two-electrode method (switchable)
Measuring frequency: 575 Hz/ 600 Hz
Measurement current: Three-electrode method: 15 mA rms or less; Two- electrode method: 3 mA rms or less
Open circuit voltage: 50 V AC rms or less
Measurement range 10 Ω (0 to 11.5 Ω) 100 Ω (0 to 115 Ω) 1000 Ω (0 to 1150 Ω)
Nominal Deviation ±0.25 Ω ±2.5 Ω ±25 Ω
Functions Auxiliary earth resistance check S (P)/ H(C)
Earth potential measurement 0 to 30 V, Nominal Deviation: ±3.0 % f.s.
Power supply LR6 (AA) Alkaline battery ×6, 1100 times operation (at 30 sec. measurement/ 30 sec. rest cycle)
Dimensions and mass 164 mm (6.46 in)W × 119 mm (4.69 in)H × 88 mm (3.46 in)D, 760 g (26.8 oz)
Included accessories Auxiliary Earthing Rod L9840 (2 piece set) ×1, Measuring cable L9841 (alligator clip, black 4 m (13.12 ft)), Measurement Cable L9842-11 (yellow 10 m (32.81 ft), equipped with winder), Measurement Cable L9842-22 (red 20 m (65.62 ft), equipped with winder) ×1, LR6 (AA) Alkaline battery ×6, Carrying Case C0106 ×1, Instruction manual ×1